ENPI, Lider në zgjidhjet Energjitike

Your trusted partner for advanced solutions in the energy sector!

40/69 kV XLPE insulated, radial and longitudinally sealed, single core cables with copper conductor

Code: N2XS(FL)2Y, CU/XLPE/LW/CWS/LW/PE

 

Standards: VDE 0276 – 632, IEC 60840 TEST STANDARDS

 

Application
These are cables with low dielectric losses used in energy networks with sudden load changes. Laid in residential or industrial areas, underground in ducts. If the cable gets water inside due to the mechanical damages, swellable tapes prevent the penetration of the water inside the cable.

 

Construction
1 Stranded copper conductors 3 XLPE insulation
2 Inner semi conductive layer 4 Outer semi conductive layer
5 Semi conductive swelling tape
6 Copper screen
7 Semi conductor swelling tape
8 PE coated aluminium foil
9 PE outer jacket

Technical Data
Max. operating temperature : 90 °C
Max. short circuit temperature : 250 °C (max. 5 sec.)
Rated voltage : 40/69 kV
Min. bending radius : 20 x D
D : Cable outer diameter