NAVY

Power cable 0,6/1 kV, PVC insulated and sheathed, with Al conductors

 

Application
Distribution power cable for static outdoor application (with protection against direct UV-irradiation), in ground, in water, within facilities, in cable canals, in concrete, in conditions where heavier mechanical loads and specially tensile strains, are not expected. Used in industrial plants, metropolitan networks and in other electric plants.

 

Standards
HRN HD 603 S1
IEC 60502-1
DIN VDE 0276 part 603

 

Construction
Conductor: Al, class 1 or 2 acc. to HRN HD 383 / IEC 60228 / DIN VDE 0295
class 1: solid, round(RE) or sector (SE)
class 2: multi wire stranded, round (RM) or sector (SM)
Insulation: PVC compound DIV-4 acc. to HRN HD 603.1, concentrically stranded cores, colour marked acc. to HRN HD 308 S2 / VDE 0293-308, with or without protective yellow-green conductor
Filler: extruded elastomer or plastomer compound or wrapped thermoplastic tapes
Sheath: PVC compound DMV-5 acc. to HRN HD 603.1
sheath colour: black

Core colour marking: HRN HD 308 S2 / VDE 0293-308

 

Technical data
Temperature range:
during installation: -5 °C up to +50 °C
fixed installed: -30 °C up to +70 °C
at short circuit of max. 5 s: up to 160 °C
Nominal voltage: Uο/U = 0,6/1 kV
Test voltage: 4 kV
Max. operating voltage in three-phase systems: 1,2 kV
Maximal tensile strength: 30 N/mm²
Behaviour in fire: IEC 60332-1
Minimal inner bending radius:
single core: 15D
multi core: 12D