Power cable 0,6/1 kV, PVC insulated and sheathed with corrugated concentric protective Cu conductor
Application
Distribution power cable for static application, mostly in ground, but also in water, within facilities, in cable canals, in concrete, in conditions requiring increased electric protection and protection against mechanical damages. Used in electric power plants, transformer stations, industrial plants, metropolitan networks and other electric plants. Concentric conductor can be used as neutral, protective or earth connection, and if there is a danger of damages caused by digging, it acts as protection against contact voltage, in case of rough insulation damage. Corrugated concentric conductor construction enables establishing of several cable connections without conductor cutting.
Standards
HRN HD 603 S1
IEC 60502-1
DIN VDE 0276 part 603
Construction
Conductor: Cu, class 1 or 2 acc. to HRN HD 383 / IEC 60228 / DIN VDE 0295
class 1: solid, round (RE)
class 2: multi wire stranded, round (RM) or sector (SM), multi wire exceeding 50 mm² are compacted
Insulation: PVC compound DIV-4 acc. to HRN HD 603.1, concentrically stranded cores, colour marked acc. to HRN HD 308 S2 / VDE 0293-308, without protective yellow-green conductor
Filler: spouted elastomer or plastomer compound or wrapped thermoplastic tapes
Concentric conductor: in inner layer corrugated spirally wrapped copper wires, in external layer copper tape wrapped in counter-helix
Sheath: PVC compound DMV-5 acc. to HRN HD 603.1
sheath colour: black
Core colour marking: HRN HD 308 S2 / VDE 0293-308
Technical data
Temperature range:
during installation: -5 °C up to +50 °C
fixed installed: -30 °C up to +70 °C
at short circuit of max. 5 s: up to 160 °C
Nominal voltage: Uο/U = 0,6/1 kV
Test voltage: 4 kV
Max. operating voltage in three-phase systems: 1,2 kV
Maximal tensile strength: 50 N/mm²
Behaviour in fire: IEC 60332-1
Minimal inner bending radius:
single core: 15D
multi core: 12D