N2XCH

Application

Power cable suitable for fixed installation in dry and damp environment, on or under plaster, on cable trays, same as in walls and concrete. Not intended for direct laying in ground or water. For outdoor application can be laid in tubes, but in that case should be taken all precautionary measures necessary to prevent water penetration into the tubes. Suitable for supply systems in an emergency. Appropriate for application in all situations where people and material goods need to be protected in case of fire. Recommended for public buildings frequented by a lot of people, and for buildings of high material value, for industrial complexes, electric power plants, transformer stations, municipal facilities, hotels, shopping malls, hospitals, schools, airports, underground railways and similar. Concentric conductor serves as electromagnetic screen, which could be applied as neutral conductor too.

advantages:
– halogen-free, no release of toxic or corrosive gases under fire
– reduced smoke occurrence under fire
– no flame propagation in vertical cable bundle

Standards

HRN HD 604 S1
DIN VDE 0276 part 604

Construction

Conductor: Cu, class 1 or 2 acc. to HRN HD 383 / IEC 60228 / DIN VDE 0295
class 1: solid, round (RE)
class 2: multi wire stranded, round (RM)
Insulation: cross-linked halogen-free polymer, 2XI1 acc. to HD 604 S1, concentrically stranded cores, colour marked acc. to HRN HD 308 S2 / VDE 0293-308, without yellow-green protective conductor
Filler: filler applied in multi core cables, extruded halogen-free polymer or halogen-free tape
Concentric conductor: in inner layer spirally wrapped round copper wires, in external layer copper tape wrapped in counter-helix
Sheath: cross-linked thermoplastic halogen-free flame retardant polyolefin bond, HM4 acc. to HD 604 S1 i VDE 0276-604
sheath colour: black
Core colour marking: acc. to HRN HD 308 S2 / VDE 0293-308

Technical data

Temperature range:
during installation:-5 °C up to +50 °C
fixed installed: -15 °C up to +90 °C
max. operating temperature: 90 °C
at short circuit of max. 5 s: up to 250 °C
Nominal voltage: Uο/U = 0,6/1 kV
Test voltage: 4 kV
Minimal inner bending radius:
single wire cables: 15D
multi wire cables: 12D
Flame retardant: IEC 60332-1
No flame propagation in vertical cable bundle: IEC 60332-3
Halogen-free: IEC 60754-1
Non-corrosive combustion gases: IEC 60754-2
Low smoke density: IEC 61034-2