NYY

Application
Distribution and signal power cable for static outdoor application (with protection against direct UV-irradiation), in ground, in water, within facilities, in cable canals, in concrete, in conditions where heavier mechanical loads and specially tensile strains, are not expected. Used in electric power plants, transformer stations, industrial plants, metropolitan networks and in other electric plants, same as for connection of signalling devices in industry, traffic and similar.

 

Standards
HRN HD 603 S1
IEC 60502-1
DIN VDE 0276 part 603 cables with 6 and more conductors:
HRN HD 627 S1
DIN VDE 0276-627

 

Construction
Conductor: Cu, class 1 or 2 acc. to HRN HD 383 / IEC 60228 / DIN VDE 0295
class 1: solid, round(RE) or sector (SE)
class 2: multi wire stranded, round (RM) or sector (SM), multi wire exceeding 50 mm² are compacted
Insulation: PVC compound DIV-4 acc. to HRN HD 603.1
Filler: extruded elastomer or plastomer compound or wrapped thermoplastic tapes
Sheath: PVC compound DMV-5 acc. to HRN HD 603.1
sheath colour: black

 

Technical data
Temperature range:
during installation: -5 °C up to +50 °C
fixed installed: -30 °C up to +70 °C
at short circuit of max. 5 s: up to 160 °C
Nominal voltage: Uο/U = 0,6/1 kV
Test voltage: 4 kV
Max. operating voltage in three-phase systems: 1,2 kV
Maximal tensile strength: 50 N/mm²
Behaviour in fire: IEC 60332-1
Minimal inner bending radius:
single core: 15D
multi core: 12D

 

Core colour marking: HRN HD 308 S2 / VDE 0293-308

Power NYY-JZ, NYY-OZ