Application
These cables are applied for fixed indoor and outdoor installation. Suitable for direct laying in ground, also resistant to UV-irradiation. They can also be laid in dry and damp environment, on or under plaster, on cable trays, same as in walls and concrete. Resistant to water sprinkling, but not intended for immersion in water. Suitable for medium mechanical loads, and specially for installations requiring increased flexibility. Suitable for electric installations with marked fire-fighting and function preserving requirements, for alarm systems, fire sensors, evacuation elevators and other supply systems in case of emergency. Appropriate for application in all situations where people and material goods need to be protected in case of fire. Recommended for public buildings frequented by a lot of people, and for buildings of high material value, for industrial complexes, electric power plants, transformer stations, municipal facilities, hotels, shopping malls, hospitals, schools, airports, underground railways and similar. It is important that these cables should not be laid on common trays, but on fire resistant trays, which retain their geometry in case of fire. Keeping the cables in the same position in case of fire, enables additional protection of cable conductivity, by means of the mineral layer discharged around the cable at increased temperature.
advantages:
– halogen-free, no release of toxic or corrosive gases under fire
– reduced smoke occurrence under fire
– no flame propagation in vertical cable bundle
– preserved electric function of the system within set time period
– easier handling and installation due to high flexibility
– possible direct laying in ground and exposure to UV-irradiation
Standards
HRN DIN 4102-12
UNE 211025
Construction
Conductor: Cu, fine wired flexible, class 5 acc. to HRN HD 383 / IEC 60228
Insulation: RZ1-K design: mica tape, fire resistant halogen-free dielectric + cross-linked halogen-free polyethylene, DIX-3 acc. to HD603
SZ1-K design: special halogen-free silicone compound, concentrically stranded cores, colour marked acc. to HRN HD 308 S2, with or without green-yellow conductor
Filler: at multi core cables, extruded halogen-free polymer
Sheath: polyolefin, halogen-free
sheath colour: orange
Core colour marking: acc. to HRN HD 308 S2 / VDE 0293-308
Technical data
Temperature range:
during installation: -5 °C up to +50 °C
fixed installed: -15 °C up to +90 °C
max. operating temperature: 90 °C
at short circuit of max. 5 s: up to 250 °C
Nominal voltage: Uο/U = 0,6/1 kV
Test voltage: 3,5 kV
Max. tensile strength of Cu conductor: 50 N/mm²
Minimal inner bending radius: 5D
Flame retardant: IEC 60332-1
No flame propagation in vertical cable bundle: IEC 60332-3
Halogen-free: IEC 60754-1
Non-corrosive combustion gases: IEC 60754-2
Low smoke density: IEC 61034-2
Insulation integrity under fire, no short circuit FE180 – fire-resistant: IEC 60331
Circuit integrity under fire – E90: acc. to DIN 4102 part 12, 90 minutes