HSLCH

Application

Halogen-free signal cable with improved properties under fire, suitable for different applications in control and measuring circuits, in industry and facilities where human lives or valuable property need to be protected against damages caused by fire. Concentric copper conductor serves as screen against electromagnetic impact. Suitable for fixed and mobile installation, but free of mechanical stress; for dry and damp environment, not for outdoor application. Resistant to majority of most frequently used oils.

advantages:
– halogen-free, no release of toxic or corrosive gases under fire
– reduced smoke occurrence under fire
– no flame propagation in vertical cable bundle

Construction

Conductor: bare copper conductor, fine wired, stranded in layers, class 5 acc. to. HRN HD 383 / IEC 60228 / DIN VDE 0295
Insulation: cross-linked halogen-free polyolefin polymer, concentrically stranded cores
Separator: polyester foil
Concentric conductor: braid of tinned copper wires, overlap >60%
Sheath: cross-linked halogen-free polyolefin polymer
sheath colour: light grey (for inst. RAL 7001 or RAL 7035)
Core colour marking: acc. to HRN HD 308 S2 / VDE 0293-308

Technical data

Temperature range:
during installation:
-5 °C up to +50 °C
fixed installed: -20 °C up to +70 °C
max. operating temperature: 70 °C
at short circuit of max. 5 s: up to 150 °C
Nominal voltage: Uο/U = 300/500 V
Test voltage: 2000 V
Minimal inner bending radius:
fixed installation: 4D
mobile installation: 15D
Flame retardant: IEC 60332-1
No flame propagation in vertical cable bundle: IEC 60332-3
Halogen-free: IEC 60754-1
Non-corrosive combustion gases: IEC 60754-2
Low smoke density: IEC 61034-2